Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
Paper
Characteristics of Single/Double-Effect Combination Absorption Refrigerator
1st Report : The Experimental Investigation about the Characteristics of Absorption Refrigerator Driven by Steam and Hot Water
Shinji KIMIJIMAShisei WARAGAITsuneo UEKUSAMasaki NAKAOSunao KAWAI
Author information
JOURNAL FREE ACCESS

1996 Volume 13 Issue 2 Pages 187-197

Details
Abstract
In recent years, co-generation system with fuel cell occupies the attention of the world from a standpoint of the environmental protection and the effective utilization of the energy. Since the waste heat of phosphoric acid fuel cell is recovered in two forms of steam (0.6 [MPa]) and hot water (65∼90 [°C]), this type of absorption refrigerator is driven by two heat sources.
In this paper, we inquire the result of the experiment intented for this absorption refrigerator the standard cooling capacity of which is 35[kW]. It is recognized that there is a mutual intervention when the supply condition of steam pressure is changed. Also the effects of hot water temperature, cooling water temperature and chilled water temperature for the performance of this absorption refrigerator is clarified. As a result, the effectiveness of using steam and hot water simultaneously in year-round operation is shown. Furthermore, it is clarified that the utilization of the low boiling temperature medium as the heat transfer medium for air-conditioner is effective.
Content from these authors
© 1996 Japan Society of Refrigerating and Air Conditioning Engineers
Previous article Next article
feedback
Top