Abstract
Application of polymeric materials for electric power apparatus is spreading worldwide. However, the aged deterioration is anxious because of dry band arc discharges generated on the surface of the polymer materials. In this paper, we carried out composite pollution tests and measured the discharge ignition time of silicone rubber. The results showed that there was no large difference in the discharge ignition times obtained between ac and dc voltage applications. Additionally, it was shown that the difference of the discharge ignition was influenced by hygroscopic property of the pollution material.